2 环氧树脂/聚酰胺配比对膨胀型钢结构防火涂料防火和抑烟性能的影响

黄丹蓉 12,颜 龙*12,李 昀 12,徐志胜 2   

  1. 1. 湖南铁院土木工程检测有限公司,长沙4100752. 中南大学土木工程学院,长沙410075
  • 出版日期:2024-03-01 发布日期:2024-03-01
  • 通讯作者: 颜龙(1987—),男,博士,副教授,主要从事防火阻燃材料的研究。
  • 基金资助:
    国家自然科学基金项目(52276143);湖南铁院土木工程检测有限公司科技开发项目(HNTY2022K07

Effect of Epoxy Resin/Polyamide Ratio on Fire and Smoke Suppression Properties of Intumescent Fire Retardant Coatings for Steel Structure

Huang Danrong1,2Yan Long12Li Yun12Xu Zhisheng2   

  1. 1. Hunan Tieyuan Civil Engineering Testing Co., Ltd., Changsha 410075,China2. School of Civil EngineeringCentral South UniversityChangsha 410075China
  • Online:2024-03-01 Published:2024-03-01

摘要:

为了增强钢结构防火涂料的防火和抑烟性能,以环氧树脂(EP/聚酰胺树脂(PA)体系作为成膜聚合物制备膨胀型钢结构防火涂料,通过锥形量热仪、烟密度仪、热重分析仪(TG)和扫描电子显微镜(SEM)等系统研究了 EP/PA 配比对膨胀型钢结构防火涂料防火和抑烟性能的影响。结果表明:钢结构防火涂料的防火和抑烟性能与EP/PA成膜聚合物体系的配比密切相关,mEP)∶mPA=32时所制备的涂层在燃烧过程中形成更多的含磷交联结构,表现出最佳的防火、抑烟和成炭效果,在 800 ℃时的残炭率达到 27. 7%,最大比光密度低至 172. 4,其保护下钢板背温达到 300 ℃所需时间为1 570 s

关键词: 膨胀型钢结构防火涂料, 环氧树脂, 聚酰胺树脂, 防火性能, 抑烟性能

Abstract: In order to enhance the fire and smoke suppression properties of fire retardant coatings for steel structure,the epoxy resinEP/polyamide resinPA system was used as the film-forming polymer to prepare intumescent fire retardant coatings. The effects and regularities of EP/PA ratio on the fire and smoke suppression properties of the intumescent fire retardant coatings for steel structure were systematically analyzed by cone heatersmoke density testerthermogravimetric analysisTG and scanning electron microscopySEM. The results showed that the fire and smoke suppression properties were closed related to the ratio of EP/PA. When the mass ratio of EP/PA was 32the obtained coating could form more phosphorus-containing cross-linking structures during combustionshowing optimal fire smoke suppression and char formation effects. The residual carbon rate of the coating at 800

Key words: intumescent fire retardant coatings for steel structure, epoxy resin, polyamide resin, fire protection, smoke suppression